No results were found for the filter!
JS- Medium voltage motor 315X2-2-200 kW-2pol-B3 Medium Voltage motor, Power= 200 kW, Speed= 3000 rpm, Construction type B3, Voltage= 6kV, Efficiency= 94.3, Paint= RAL 5010 (gentian blue), Degree of protection= IP54, Shaft 65 x 140mm, Temperature sensor= 3 x PTC thermistors, Weight=...
JS- Medium voltage motor 315X2-4-200 kW-4pol-B3 Medium Voltage motor, Power= 200 kW, Speed= 1500 rpm, Construction type B3, Voltage= 6kV, Efficiency= 94.3, Paint= RAL 5010 (gentian blue), Degree of protection= IP54, Shaft 80 x 170mm, Temperature sensor= 3 x PTC thermistors, Weight=...
JS- Medium voltage motor 315X2-6-200 kW-6pol-B3 Medium Voltage motor, Power= 200 kW, Speed= 1000 rpm, Construction type B3, Voltage= 6kV, Efficiency= 93.4, Paint= RAL 5010 (gentian blue), Degree of protection= IP54, Shaft 80 x 170mm, Temperature sensor= 3 x PTC thermistors, Weight=...
JS- Medium voltage motor 315X4-2-250 kW-2pol-B3 Medium Voltage motor, Power= 250 kW, Speed= 3000 rpm, Construction type B3, Voltage= 6kV, Efficiency= 94.4, Paint= RAL 5010 (gentian blue), Degree of protection= IP54, Shaft 65 x 140mm, Temperature sensor= 3 x PTC thermistors, Weight=...
JS- Medium voltage motor 315X4-4-250 kW-4pol-B3 Medium Voltage motor, Power= 250 kW, Speed= 1500 rpm, Construction type B3, Voltage= 6kV, Efficiency= 94.5, Paint= RAL 5010 (gentian blue), Degree of protection= IP54, Shaft 80 x 170mm, Temperature sensor= 3 x PTC thermistors, Weight=...
JS- Medium voltage motor 355X1-6-250 kW-6pol-B3 Medium Voltage motor, Power= 250 kW, Speed= 1000 rpm, Construction type B3, Voltage= 6kV, Efficiency= 93.6, Paint= RAL 5010 (gentian blue), Degree of protection= IP54, Shaft 100 x 210mm, Temperature sensor= 3 x PTC thermistors, Weight=...
JS- Medium voltage motor 355X1-2-315 kW-2pol-B3 Medium Voltage motor, Power= 315 kW, Speed= 3000 rpm, Construction type B3, Voltage= 6kV, Efficiency= 94.6, Paint= RAL 5010 (gentian blue), Degree of protection= IP54, Shaft 75 x 140mm, Temperature sensor= 3 x PTC thermistors, Weight=...
JS- Medium voltage motor 355X1-4-315 kW-4pol-B3 Medium Voltage motor, Power= 315 kW, Speed= 1500 rpm, Construction type B3, Voltage= 6kV, Efficiency= 94.6, Paint= RAL 5010 (gentian blue), Degree of protection= IP54, Shaft 100 x 210mm, Temperature sensor= 3 x PTC thermistors, Weight=...
JS- Medium voltage motor 355X3-6-315 kW-6pol-B3 Medium Voltage motor, Power= 315 kW, Speed= 1000 rpm, Construction type B3, Voltage= 6kV, Efficiency= 94.0, Paint= RAL 5010 (gentian blue), Degree of protection= IP54, Shaft 100 x 210mm, Temperature sensor= 3 x PTC thermistors, Weight=...
JS- Medium voltage motor 400X2-8-315 kW-8pol-B3 Medium Voltage motor, Power= 315 kW, Speed= 750 rpm, Construction type B3, Voltage= 6kV, Efficiency= 94.1, Paint= RAL 5010 (gentian blue), Degree of protection= IP54, Shaft 110 x 210mm, Temperature sensor= 3 x PTC thermistors, Weight=...
JS- Medium voltage motor 355X2-2-355 kW-2pol-B3 Medium Voltage motor, Power= 355 kW, Speed= 3000 rpm, Construction type B3, Voltage= 6kV, Efficiency= 94.7, Paint= RAL 5010 (gentian blue), Degree of protection= IP54, Shaft 75 x 140mm, Temperature sensor= 3 x PTC thermistors, Weight=...
JS- Medium voltage motor 355X2-4-355 kW-4pol-B3 Medium Voltage motor, Power= 355 kW, Speed= 1500 rpm, Construction type B3, Voltage= 6kV, Efficiency= 94.7, Paint= RAL 5010 (gentian blue), Degree of protection= IP54, Shaft 100 x 210mm, Temperature sensor= 3 x PTC thermistors, Weight=...
High-end medium voltage motors
These large industrial motors are available with powers up to 40 000 kW and are operated using medium voltage.
These motors are usually special motors made to customers’ specifications. Their number of poles is
between 2 and 20. Available protection classes are IP23 and IP55 to IP 65.

Medium voltage motor with air cooling
Cooling types
IC 411, fin cooled
IC 611, with air-to-air heat exchanger
IC 81W, with air-to-water heat exchanger
IC 01, open-circuit ventilated

Slip ring rotor - medium voltage motor
Common rated voltages
50 Hz: 2000V / 3000V / 3300V / 5000V/ 5500V / 6000V / 6300V/ 6600V / 10000V / 10500V / 11000V
60 Hz: 4160 V / 13800 V. The admissible voltage tolerance is ± 5%. Special voltages and different
voltage tolerances are available on request.

Medium voltage motor with tube cooling
Tests
The following engine tests are optionally carried out in the factory:
High voltage test, checking the sense of rotation, measuring the winding resistance, insulation resistance test,
resting under no load, short-circuit test, vibration strength test, measuring the shaft tension, function check
of accessories, noise measurement; check for visible damage and documentation. If required, testing under
full load, heating test, momentum test and dissipation factor measurement are possible.

Rib-cooled medium voltage motor with terminal box on top
Motor overload protection / monitoring
The medium-voltage motors can be supplied with temperature monitoring for windings and bearings, e.g. 6 Pt100
resistance thermometers in the stator winding, 2 Pt100 resistance thermometers in the A-side and B-side bearings.
The terminals of the resistance thermometers are located in a separate terminal box. More over a large spectrum
of further sensors can be supplied on request. The majority of the motors supplied are equipped with
anti-condensation heating.
SEO= Individual Medium Voltage Motors,High-end medium-voltage motors